7313 William Barry Blvd. North Syracuse, NY 13212- Toll Free (800) 365-5525 - info@icmcontrols.com
made in the usa
Cross Reference Search:

ICM284

Description

The ICM284 control is microprocessor based using software to determine the sequence of operation, timing, trial for ignition, flame sensing and lockout. The control monitors the status of the room thermostat, limit and rollout switches, air pressure switch and flame sensor before enrgizing the vent motor, blower control, hot surface ignitor and gas valve. The control provides diagnostic codes (flashing LEDs) to aid in testing and troubleshooting.

  • Low cost, direct replacement board for York S1-03101280000 
  • Controls vent motor, blower control, hot surface ignitor and gas valve
  • Designed for 100% gas shutoff in case of ignition failure
  • Monitors timing, trial for ignition, flame sensing and lockout
  • Diagnostic LEDs aid in testing / troubleshooting 

Specifications

Line Voltage Range: 208 VAC @ 60Hz

Ignitor: 5A resistive @ 208 VAC

Cool Blower: 30A, 2HP, 240 VAC

Heat Blower: 10A, 1/2HP, 250 VAC

Inducer Motor: 4A, 208 VAC

Gas Valve: 4A @ 24 VAC

Compressor: 5A resistive @ 24 VAC

Downloads

Sell Sheet Installation Guide

Related Products

Other Products to Consider