ICM (Obsolete/Legacy Products)
ICM2901
ICM (Obsolete/Legacy Products)
ICM2901
JCI/York OEM Replacement Control
The ICM2901 Intermittent Pilot Gas Ignition Control Module provides easy field replacement of Johnson Control: G770RJA-1, York: 025-27762-700 and comparable ignition controls.Electrical
- Control Voltage: Line 24 VAC (18-30 VAC) 50/60 Hz
- Anticipator Setting: 0.3A plus valve load @ 24 VAC
- Pre-purge: None
- Trial for Ignition: 85 seconds
- Retry: None
Environment
- Operating Temperature:
- Min. ambient temperature rating is -40°F (-40°C)
- Max. ambient rating when used with 2.0A main valve is 160°F (71°C)
- Relative Humidity: 0% to 95% non-condensing
Weight/Dimensions
- Weight: 0.5 lb.
- Height: 1.875″
- Width: 3.125″
- Length: 4.75″
ICM: 294
Johnson Controls: G770RJA-1
York: 025-27762-700 and comparable ignition controls