JCI/Lennox OEM Replacement Control
  • Intermittent pilot gas ignition control
  • For use with intermittent pilot boilers, furnaces and other heating appliances
  • Microprocessor-based precision
  • Monitors timing, trial for ignition, flame sensing and lockout
  • Remote flame sensing
  • 100% lockout safety feature
  • Works with both Natural and LP gas systems
  • Status LED for fault codes to aid in troubleshooting

Electrical

  • Control Voltage: Line 24 VAC (18-30 VAC) 50/60 Hz
  • Anticipator Setting: 0.3A plus valve load @ 24 VAC
  • Pre-purge: 15 seconds
  • Trial for Ignition: 85 seconds
  • Lockout: 60 minutes
  • Flame Failure Response Time: 2 seconds
  • Status LED: See product label for error codes

Environment

  • Operating Temperature:
    • Minimum ambient temperature rating is -40°F (-40°C)
    • Maximum ambient rating when used with 2.0A main valve is 165°F (74°C)
  • Relative Humidity: 0% to 95% non-condensing
Weight/Dimensions
  • Weight: 0.5 lb.
  • Height: 1.875″
  • Width: 3.125″
  • Length: 4.75″
Sell Sheet
Download
Application/Install Guide
Download

ICM: 293

Johnson Controls: G776 (63K2401, 41K8701, 69J3601)

Lennox: 30W33