ICM (Obsolete/Legacy Products)
ICM2902
ICM (Obsolete/Legacy Products)
ICM2902
JCI/Lennox OEM Replacement Control
Electrical
- Control Voltage: Line 24 VAC (18-30 VAC) 50/60 Hz
- Anticipator Setting: 0.3A plus valve load @ 24 VAC
- Pre-purge: 15 seconds
- Trial for Ignition: 85 seconds
- Lockout: 60 minutes
- Flame Failure Response Time: 2 seconds
- Status LED: See product label for error codes
Environment
- Operating Temperature:
- Minimum ambient temperature rating is -40°F (-40°C)
- Maximum ambient rating when used with 2.0A main valve is 165°F (74°C)
- Relative Humidity: 0% to 95% non-condensing
Weight/Dimensions
- Weight: 0.5 lb.
- Height: 1.875″
- Width: 3.125″
- Length: 4.75″
ICM: 293
Johnson Controls: G776 (63K2401, 41K8701, 69J3601)
Lennox: 30W33
Robertshaw: 735L (18G91), 745 (95H04)