Reznor OEM Replacement Control
Intermittent pilot gas ignition control module for use with intermittent pilot boilers, furnaces and other heating appliances. Monitors timing, trial for ignition, flame sensing and lockout.Electrical
- Control Voltage: 18-30 VAC
- Frequency: 50/60 Hz
- Operating Temperature: -40°F to 165°F, -40°C to 75°C
- Current Draw: 100 mA maximum
- Pre-Purge Delay: 0 seconds
- Trial for ignition: 2-minutes
- Lock Out Time: 60-minutes
Weight/Dimensions
- Weight: 0.45 lb.
- Height: 2″
- Width: 5.3″
- Length: 4″
Reznor: 257010