Air Handling Controller
Fan Controls

ICM6501

Share:
Air Handling Controller
Fan Controls

ICM6501

ClimaTek Air Handling Replacement Control
The ICM6501 air handler control board operates with hot water heating systems. When the thermostat calls for Heat, the control will energize the Water Pump, Valve and Boiler. The blower will energize at the selected speed after 90 seconds to allow the coil to preheat.
  • Input Voltage: 24 VAC, 120/240 VAC, 50/60 Hz
  • Valve Output: 24 VAC, 50/60 Hz, 5A
  • Blower Fan: 120/240 VAC, 50/60 Hz, 9.8 FLA
  • Water Pump: 120/240 VAC, 50/60 Hz, 1.5 FLA
  • Boiler:  24 VAC, 50/60 Hz, 5A
  • Timing
    • Fan on delay: 0 secs
    • Fan off delay: 45 secs
    • Heat fan on delay: 90 secs
    • Heat fan off delay: 20 secs
  • Surrounding Air Temperature Rating:  -40ºF to 167ºF  (-40ºC to 75ºC)
Weight/Dimensions
  • Weight: 1
  • Height: 1
  • Width: 2.5
  • Length: 7
Sell Sheet
Download
Application/Install Guide
Download

Replaces:

ClimaTek: CB201

First Company: CB201